Wiring UFO High Bays in Parallel: A Daisy-Chain Guide

Richard Miller |

Technical Guide: Parallel Wiring and Electrical Engineering for Industrial UFO High Bay Lights

Technical Disclosure: This guide is produced to provide engineering and installation best practices. While this article may reference specific components or vendors as examples of industry standards, readers should evaluate all products based on their specific project requirements and local electrical codes. High-Hyperlite provides this information as a resource; however, all electrical work should be performed by licensed professionals.

Parallel wiring is the industry-standard architecture for industrial lighting, designed so that the failure of a single luminaire does not compromise the entire circuit’s integrity. However, transitioning from a simple diagram to a high-performance warehouse installation requires rigorous attention to voltage drop, harmonic distortion, and compliance with the National Electrical Code (NEC).

The primary technical objective for any large-scale facility is to support parallel daisy-chaining with precise American Wire Gauge (AWG) selection and individual fixture protection. By following a structured electrical design, facility managers can achieve a system optimized for a Total Cost of Ownership (TCO) that, in specific high-usage scenarios, may see a return on investment (ROI) in under one year.

The Physics of Parallel Circuits in Industrial Lighting

In a parallel circuit, every luminaire is connected to the same two nodes, ensuring that each fixture receives the full source voltage. This is in contrast to series wiring, where voltage is divided among loads—a configuration unsuitable for modern LED drivers.

While parallel wiring provides the benefit of independent operation, it introduces the challenge of cumulative voltage drop. As the length of the wire run increases, the resistance of the copper conductor causes a decrease in voltage. According to standard electrical circuit analysis, exceeding a 3% voltage drop on branch circuits is generally discouraged by NEC Informatory Note 210.19(A), as it can lead to LED driver instability, visible flickering, or reduced component lifespan.

Formula: Calculating Voltage Drop

To determine the precise wire gauge needed, engineers use the following formula for single-phase AC circuits: $$V_{drop} = \frac{2 \cdot L \cdot R \cdot I}{1000}$$ Where:

  • L = One-way length of the circuit (feet)
  • R = Resistance of the conductor (Ω per 1,000 feet, per NEC Chapter 9, Table 8)
  • I = Load current (Amps)

Example Calculation: For a 150ft run of 12 AWG copper ($R \approx 1.98 \Omega/1000ft$) carrying a 16A load at 120V: $$V_{drop} = \frac{2 \cdot 150 \cdot 1.98 \cdot 16}{1000} = 9.5V$$ Result: 9.5V is a 7.9% drop, which exceeds the recommended 3% limit (3.6V). This scenario would require upgrading to 8 AWG or increasing the system voltage to 277V.

AWG Selection Matrix (Estimated Guidelines)

Note: These values assume a 3% maximum drop at 120V. For 277V systems, allowable distances significantly increase.

Wire Gauge (AWG) Max Circuit Load (Amps) Recommended Max Run (ft) Voltage Drop Risk Profile
14 AWG 15 < 50 High (Significant drop after 50ft at 120V)
12 AWG 20 50 – 90 Moderate (Standard for mid-sized shops)
10 AWG 30 90 – 150 Low (Best for large logistics hubs)

UFO LED High Bay light illuminating a metal pole‑barn — LED shop lights for warehouse and garage retrofit

NEC Compliance and Safety Standards

Professional installations must adhere to the National Electrical Code (NEC) - NFPA 70. Article 410 of the NEC governs the installation of luminaires, providing specific mandates for spacing and support.

Spacing and Photometric Integrity

A standard requirement for industrial facilities is maintaining specific spacing ratios to ensure uniform illuminance. According to the IES RP-7-21 Recommended Practice for Industrial Facilities, high-ceiling spaces (typically 20–40 feet) require a spacing-to-mounting-height ratio that avoids "hot spots" or dark zones.

For most UFO-style fixtures with a 120° beam angle, a spacing of 1.2 to 1.5 times the mounting height is a common pragmatic baseline. However, for precise layouts, installers should utilize .ies files within software like AGi32 or DIALux to simulate light distribution before wiring begins.

Safety and Certification (UL/ETL)

Every component in the daisy chain should meet North American safety standards. The UL 1598 standard for luminaires ensures that the fixture's housing and thermal management can withstand 24/7 operation. Using non-certified fixtures in a parallel chain is a liability risk; a single thermal event in a low-quality driver can potentially damage the entire circuit.

LED High Bay lights in a high‑ceiling warehouse with tablet displaying lighting layout and beam patterns

Practical Daisy-Chaining: Tools and Techniques

The mechanical execution of the parallel connection is a common point of failure. Traditional wire nuts can loosen over time due to building vibrations or thermal cycles.

  • The WAGO Advantage: Many contractors recommend WAGO lever-nut connectors over traditional twist-on nuts. Lever-nuts provide a vibration-resistant connection and allow for easier troubleshooting.
  • Torque and Continuity: When using terminal blocks, a torque screwdriver is recommended to meet manufacturer specifications. Over-tightening can damage copper strands, while under-tightening leads to arcing.
  • Grounding: Before energizing, perform a continuity test between the ground pin of the first fixture and the last. An unbroken grounding path is a mandatory safety requirement for Designing a High Bay Layout for Warehouse Safety.

The "Pro" Audit: Harmonics and Circuit Protection

A non-obvious pitfall in large LED installations is Total Harmonic Distortion (THD). LEDs are non-linear loads; their drivers can introduce harmonic frequencies into the system.

Mixed Fixture Risks

Mixing different brands or ages of fixtures on a single parallel circuit can exacerbate harmonic issues. Field measurements in facilities with mixed-driver environments have recorded THD levels exceeding 30%, which can interfere with sensitive electronics like facility servers. If performing a phased retrofit, a harmonic analysis is recommended.

Individual Fixture Fusing

While the branch circuit is protected by a breaker, a parallel chain benefits from individual fixture fusing. This ensures that if a single driver fails, it blows its own fuse rather than tripping the main breaker and plunging the entire floor into darkness. This is vital in facilities requiring 24/7 operation where UFO high bays for task lighting are critical.

Economic Impact: The 50,000 Sq Ft Scenario

To demonstrate the potential impact of a correctly engineered system, consider this simulation of a 50,000 sq ft logistics warehouse.

Calculation Assumptions:

  • Existing System: 40 units of 458W Metal-Halide fixtures.
  • Proposed System: 40 units of 300W LED UFO High Bays.
  • Utility Rate: $0.12 per kWh.
  • Operation: 24/7 (8,760 hours/year).
  • Rebates: Estimated $50 per fixture (Utility prescriptive rebate).
Metric Value
Annual Energy Savings ~99,654 kWh
Annual Energy Cost Reduction $11,958
Maintenance Savings (Est.) $3,854
Total Annual Savings $15,812
Net Project Cost (After Rebates) $11,000
Calculated Payback Period 0.7 Years

Note: Actual ROI varies based on local labor rates, specific utility rebate programs, and actual energy costs.

Worker installing LED High Bay lights (LED shop lights) in a high-ceiling industrial workshop from a scissor lift

Troubleshooting and Maintenance Patterns

  1. Uniform Dimming at the End of the Chain: Typically a symptom of voltage drop. Re-measure voltage at the last fixture under load. If the drop exceeds 3-5%, consider upsizing the home-run wire.
  2. Random Flickering: Often points to THD or interference from large motors or HVAC compressors on the same phase. Ensure lighting circuits are dedicated.
  3. Single Fixture Failure: If the rest of the chain remains lit, the parallel wiring is intact. Check the individual fixture’s connection points. Using WAGO connectors can make this diagnostic step significantly faster.

Professional Installation Checklist

  • Calculations: Are voltage drop calculations documented for runs exceeding 100 feet?
  • Hardware: Are WAGO lever-nuts or torqued terminal blocks utilized?
  • Compliance: Does every fixture carry a UL or ETL mark?
  • Protection: Is the grounding path verified by a continuity test?
  • Controls: Are occupancy sensors integrated to meet ASHRAE 90.1 energy standards?

Parallel wiring is the foundation of a reliable industrial environment. By bridging the gap between electrical theory and professional-grade execution, facility managers can help ensure their lighting systems remain a high-value asset for years to come.


Disclaimer: This article is for informational purposes only and does not constitute professional electrical or legal advice. Electrical work involves significant risks, including fire and electrocution. All installations must be performed by a licensed electrician in accordance with the National Electrical Code (NEC) and local building codes.